  • Product description: SL360-63A Residual Current Circuit Breaker RCCB
  • INQUIRY

SL360-63A residual current operated circuit breaker(RCCB) introuction

SL360-63A residual current operated circuit breaker (residual current breaker) is suitable for AC 50 Hz, rated voltage two pole 240V, four pole 415V, rated current up to 63A line, When personal electric shock or grid leakage current exceeds the specified value,residual current operated circuit breaker (residual current breaker) can quickly cut off the fault power supply in a very short time, protect the safety of personal and electrical equipment, and can also be used for infrequent line conversion.


SL360-63A residual current breaker (RCCB) Scope of application

SL360-63A residual current breaker (RCCB) are suitable for industrial, commercial, high-rise and residential buildings.


1.Protection against the effects of sinusoidal alternating earth fault currents
2.Protection against indirect contacts and additional protection against direct contacts
3.Protection against fire hazard caused by insulation faults
4.Controlling and Switching
5. Used in residential building, non-residential building, energy sources, industry  Used in residential building, non-residential building, energy sources, industry


SL360-63A residual current breaker (RCCB)  Specification


Type Standard IEC/EN 61008-1
Electrical features Leakage type
Electromagnetic type
Rated current In A 16, 25, 32,40, 50, 63, 80,100
Type (wave form of the earth leakage sensed)
A, AC
Poles P 2,4
Rated voltage Ue V 240/415
Insulation voltage Ui V 500
Rated frequency Hz 50/60
Rated breaking capacity Inc=Ic A 4500,6000
SCPD fuse A 6000
Rated impulse withstand voltage (1.2/50) Uimp V 6000
Dielectric test voltage at ind. Freq, for lmin kV 2.5
Rated sensitivity I?n A 0.03, 0.1, 03
Rated residual making and breaking capacity Im A 500(In<40A); 630(In >40A)
Pollution degree
2
Mechanical features Electrical life t 4000
Mechanical life t 8000
Protection degree
IP20
Storage temperature °C 25~+70
Ambient temperature (with daily averages35°C) °C -5-+40
Installation Terminal connection type
Cable/U-type bar/Pin-type busbar
Terminal size top / bottom for cable mm2 25
AWG 18-3
Terminal size top / bottom for busbar mm2 25
AWG 18-3
Tightening torque N*m 2.5
In-Ibs 18
Mounting On DIN rail EN 60715(35mm)by means of fast clip device
Connection
From top and bottom


SL360-63A residual current breaker (RCCB)  Electric drawing